Single/three phase power & energy datalogger designed for electricians, facilities engineers, contractors and energy professionals who need to record electrical or energy use over time. Includes on-board display
This product is ideal for electricians, engineers and contractors doing work in the area of building and system monitoring and upgrades, as well as residential energy audits. All vital energy data is easily measured, recorded, analyzed and reports generated with confidence and minimal configuration time and effort.
The PEL 103 has many up-to-date features demanded by the present market conditions.
The package is laid out in such a way that it can be installed in a load center panel including the current sensors and still allow the door to close on most panels. The PEL 103 offers all the essential functions for data logging Power/Energy from most of the electrical power networks in use today. The PEL 103 energy loggerss measures three voltage and three current inputs and records these inputs as well as Watts, VARS, VA and energy (kWh, kvarh and kVA). Power factor, displacement power factor, crest factor, frequency and THD are calculated and recorded as well. Individual harmonic information including value, % and phase angle out to the 50th harmonic is also recorded at the operator's choice. All variables are recorded and stored on a one second basis and on user selectable demand intervals from one to sixty minutes. Energy costs can be calculated and displayed quickly and easily by simply programming in the unit cost for a kilowatt hour. Data is stored on internal memory or on a removable SD card. Data can be retrieved by USB, Bluetooth and/or Ethernet (local or internet) connection as well as transporting the SD card back to the download site.
The included, comprehensive DataView® software also provides the ability to view data from several hundred PEL units on a local network or over the internet providing the ability to evaluate energy usage on a department or facility basis anywhere in the world. Real-time data can be reviewed as well as downloading stored results for analysis and report generation.
Configuration of the PEL 103 instruments takes place through the DataView® software either locally or remotely. Most of the configured parameters are pre-set in the instrument keeping the user interface simple and straightforward and easy to complete in a few minutes. Current probes are automatically defined and calibrated when they are plugged into the unit. User selections include network type, demand interval, recording length, voltage and current ratios where necessary, recording duration (defined either by time and/or date) and communication method. Pass word protection can be initiated for Bluetooth and network communication to guard against unauthorized access and protection of data integrity.
The DataView® software provides the ability to review power, harmonic and RMS data in real time and to download recorded sessions for more extensive analysis and report generation. One second trend and demand interval trend graphs and tabular listings can be displayed and printed out. Energy costs can be calculated. Source and load graphs can be plotted. Individual phase and the sum of all phases can be evaluated. Once on screen, the user has access to a variety of analytical tools to analyze individual data points or sections of the recorded data without the frustration with having to deal with layers of button pushing to get to the information you need.
This simple to use yet comprehensive power and energy logger will be an invaluable asset to your energy monitoring and analysis.
| GENERAL | |||
| Data Storage Rate | 1 per second | ||
| Demand Period Storage Rate | User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes) | ||
| Recorded Parameters (Single- and Poly-Phase) |
V, I, W, VA, var, PF, Tan, Wh, Vah, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF |
||
| Event Log | Tracks and records status changes and error messages along with recorded data | ||
| Front Panel Indicator LEDs | Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status | ||
| Storage Capacity | 2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB) formatted FAT32 are supported | ||
| INPUTS | |||
| Voltage | 3 voltage input channels via 4mm safety banana jacks | ||
| Current | 3 current input channels via custom 4 pin jacks that accept AEMC® probes and sensors shown on page 5 | ||
| ELECTRICAL | |||
| Voltage Measurement | Range | Resolution | *Accuracy (% of Reading) |
| 50/60Hz | 42.5 to 69Hz | - | ±0.1Hz |
| Single-Phase RMS Voltages | 100 to 1000 rms | 0.1V | ±0.2% Rdg ±0.2V |
| Phase-to-Phase RMS Voltages | 100 to 2000Vrms | 0.1 to 1V | ±0.2% Rdg ±0.4V |
| 400Hz | 340 to 460Hz | - | - |
| Single-Phase RMS Voltages | 100 to 600Vrms | 0.1V | ±1% Rdg ±1V |
| Phase-to-Phase RMS Voltages | 200 to 1200Vrms | 0.1 to 1V | ±1% Rdg ±1V |
| DC | 100 to 1000V | 0.1V | ±1% Rdg ±3V (typical) |
| PT Ratios | Programmable from 50V to 65,0000V (primary and secondary) |
0.01V to 0.1V | - |
| CURRENT MEASUREMENT | |||
| Current Probe: MiniFlex® Sensor MA193 For further specifications and other compatible current probes, see chart on page 5 |
5 to 100Arms | 1 to 100mA | ±1% ± 50mA |
| 20 to 400Arms | 10 to 100mA | ±1% ± 0.2A | |
| 100 to 2000Arms | 0.1 to 1A | ±1% ± 1A | |
| 500 to 10,000Arms | 0.1 to 1A | ±1% | |
| CT Ratios | Programmable from 1:1 to 25,000:1 (probe dependent) | ||
| POWER MEASUREMENTS | |||
| Active Power (P)* | -2 to 2GW | 0.001W | ±0.5% Rdg ± 0.005% Pnom |
| Reactive Power (Q)* | -2 to 2Gvar | 0.001var | ±1% Rdg ± 0.01% Qnom |
| Apparent Power (S)* | 0 to 2GVA | 0.001VA | ±0.5% Rdg ± 0.005% Snom |
| Power Factor | -1 to + 1 | 0.001 | ± 0.05 |
| Tangent F (active/reactive power ratio) |
-3.2 to +3.2 | 0.001 | ± 0.02 |
| ENERGY MEASUREMENTS | |||
| Active Energy (EP) | 0 to 4EWh | 1Wh | ±0.5% Rdg |
| Reactive Energy(EQ) | 0 to 4EWh | 1varh | ±2% Rdg |
| Apparent Energy (ES) | 0 to 4EWh | 1Vah | ±0.5% Rdg |
| HARMONICS | |||
| THD | +/- 655% | ||
| Individual Harmonics | 1 to 50 displayed in percentage; 1 to 7 at 400Hz | ||
| MECHANICAL | |||
| Communication Ports | USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 | ||
| Dimensions/Weight | 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / <1kg | ||
| Case / Index of Protection | Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / Yes / IP54 non operating | ||
| Mounting | Embedded magnets on back side, keyhole slot on back side | ||
| Security | Kensington anti-theft system | ||
| External Supply | 110V/250V (10%) @ 50/60Hz; 1-7 (400Hz) | ||
| Back-Up Power Source / Charge Time | Rechargeable 8.4V NiMH battery pack / Approximately 5 hours | ||
| Battery Life | Provides up to 30 minute ride through upon power loss | ||
| DISPLAY | |||
| Display Type | 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness and contrast | ||
| ENVIRONMENTAL | |||
| Operating Temperature / Relative Humidity | 32° to 122°F (0° to 50°C) / up to 85% | ||
| Storage Temperature | -4° to 122°F (-20° to 50°C) with batteries; -4° to 158°F (-20° to 70°C without batteries) | ||
| SAFETY | |||
| Safety Rating / CE Rating | Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III/ 600V CAT IV, Pollution Degree 2 / Yes |