AEMC F05 Clamp-on Meter (TRMS, 400AAC/DC, 600VAC/DC, Hz, Power (kW), Phase Rotation, Ohms, Continuity)
The AEMC F05 is a high performance clamp-on meter built into a rugged compact sized case, with exceptional ergonomic design and extraordinary measurement possibilities.
Integrating a fast microprocessor sampling at a high rate, the F05 is completely automatic and performs TRMS measurements on the most distorted waveforms. The Model F05 automatically detects AC or DC in Voltage and Current. It has a V-Live™ function to warn of the use of live circuits or elevated voltages. The Model F05 can measure in-rush currents from 1 cycle up to 10 cycles and frequency. It also measures Phase Rotation (using only two leads!), Power Factor and Power. Other features include: auto-ranging, 4000-count display and Auto-Off.
| Electrical | |
| Measurement Range | 40V: 0.2 to 39.99V / 400V: 40.0 to 399.9V / 4000V: 400 to 600V (400 to 900V pk) |
| Accuracy | 40V: 1% of reading + 5cts / 400V: 1% of reading + 2cts / 4000V: 1% of reading + 2cts |
| Continuity | |
| Measurement Range | 0.0 to 399.9Ω; |
| Accuracy | 1% of reading + 2cts |
| Resistance | |
| Measurement Range | 400Ω: 0.0 to 399.9Ω / 4000Ω: 400 to 3999Ω / 40000Ω: 4.0 to 39.99kΩ; |
| Accuracy | 1% of reading + 2cts |
| Diode | |
| Measurement Range | 4V: 0 to 3.199V |
| Current | |
| Measurement Range | 40A: 0.20 to 39.99A / 400A: 40 to 399.9A / 4000A: 400 to 600A pk |
| Accuracy | 40A: 1.5% of reading + 10cts / 400A: 1.5% of reading + 2cts / 4000A: 1.5% of reading + 2cts |
| Resolution | 40A: 10mA / 400A: 100mA / 4000A: 1A |
| Inrush Function | |
| Range for use | ≥5A pk for the first period of the signal |
| Accuracy | 5% + 0.5A |
| Capture Time | 0.5 to 10 periods of the signal frequency (8 to 160ms at 60Hz) |
| Power | |
| Measurement Range | 4kW: 5 to 3999W / 40kW: 4.00 to 39.99kW / 400kW: 40.0 to 240kW |
| Power Factor Calculation | |
| Measurement Range | 1.00: 0.20 to 0.49 / 0.50 to 1.00 / Accuracy 5% of reading + 2cts / 2% of reading + 2cts |
| Frequency | |
| Measurement Range | 40Hz: 10.00 to 39.99Hz / 400Hz: 40.0 to 399.9Hz / 4000Hz: 400 to 3999Hz / 40000Hz: 4.00 to 19.99kHz |
| Accuracy | 40Hz - 40kHz: 0.4% of reading + 1ct |
| General | |
| Display | 4 digits, 9999 counts, 3 decimal points, "+" & "-" signs (DC and peak measurement) |
| Operating Temperature | 32° to 122°F (0° to 50°C); 90% RH |
| Storage Temperature | 40° to 158°F (-40° to 70°C); 90% RH |
| Power Source | 9V Alkaline Battery (type IEC 6LF22, 6LR61, or NEDA 1604) |
| Jaw Opening | ≤1.00" (≤26mm) |
| Dimensions | 2.76 x 7.6 x 1.46" (70 x 193 x 37mm) |
| Weight | 9.17 oz (260g) |
| Safety | |
| Safety Rating | EN62020-1, EN61010-2-032, 600V CAT III |
| CE Mark | Yes |