The AEMC F05 is a high performance clamp-on meter built into a rugged compact sized case, with exceptional ergonomic design and extraordinary measurement possibilities.

Integrating a fast microprocessor sampling at a high rate, the F05 is completely automatic and performs TRMS measurements on the most distorted waveforms. The Model F05 automatically detects AC or DC in Voltage and Current. It has a V-Live™ function to warn of the use of live circuits or elevated voltages. The Model F05 can measure in-rush currents from 1 cycle up to 10 cycles and frequency. It also measures Phase Rotation (using only two leads!), Power Factor and Power. Other features include: auto-ranging, 4000-count display and Auto-Off.


Applications

  • Electrical maintenance
  • Electrical power distribution
  • Safety lighting system maintenance
  • Automotive test troubleshooting
  • Industrial maintenance
  • HVAC

Specifications

Electrical
Measurement Range 40V: 0.2 to 39.99V / 400V: 40.0 to 399.9V / 4000V: 400 to 600V (400 to 900V pk)
Accuracy 40V: 1% of reading + 5cts / 400V: 1% of reading + 2cts / 4000V: 1% of reading + 2cts
Continuity
Measurement Range 0.0 to 399.9Ω;
Accuracy 1% of reading + 2cts
Resistance
Measurement Range 400Ω: 0.0 to 399.9Ω / 4000Ω: 400 to 3999Ω / 40000Ω: 4.0 to 39.99kΩ;
Accuracy 1% of reading + 2cts
Diode
Measurement Range 4V: 0 to 3.199V
Current
Measurement Range 40A: 0.20 to 39.99A / 400A: 40 to 399.9A / 4000A: 400 to 600A pk
Accuracy 40A: 1.5% of reading + 10cts / 400A: 1.5% of reading + 2cts / 4000A: 1.5% of reading + 2cts
Resolution 40A: 10mA / 400A: 100mA / 4000A: 1A
Inrush Function
Range for use ≥5A pk for the first period of the signal
Accuracy 5% + 0.5A
Capture Time 0.5 to 10 periods of the signal frequency (8 to 160ms at 60Hz)
Power
Measurement Range 4kW: 5 to 3999W / 40kW: 4.00 to 39.99kW / 400kW: 40.0 to 240kW
Power Factor Calculation
Measurement Range 1.00: 0.20 to 0.49 / 0.50 to 1.00 / Accuracy 5% of reading + 2cts / 2% of reading + 2cts
Frequency
Measurement Range 40Hz: 10.00 to 39.99Hz / 400Hz: 40.0 to 399.9Hz / 4000Hz: 400 to 3999Hz / 40000Hz: 4.00 to 19.99kHz
Accuracy 40Hz - 40kHz: 0.4% of reading + 1ct
General
Display 4 digits, 9999 counts, 3 decimal points, "+" & "-" signs (DC and peak measurement)
Operating Temperature 32° to 122°F (0° to 50°C); 90% RH
Storage Temperature 40° to 158°F (-40° to 70°C); 90% RH
Power Source 9V Alkaline Battery (type IEC 6LF22, 6LR61, or NEDA 1604)
Jaw Opening ≤1.00" (≤26mm)
Dimensions 2.76 x 7.6 x 1.46" (70 x 193 x 37mm)
Weight 9.17 oz (260g)
Safety
Safety Rating EN62020-1, EN61010-2-032, 600V CAT III
CE Mark Yes

Ask a Question about the F05